A5E32268590 SITRANS LC300 – QUICK START MANUAL Page EN-5
mmmmm
English
Mounting Location
Recommendations
Easy access for programming the unit using the rotary switch and buttons.
An environment suitable to the housing rating and materials of construction.
Precautions
Keep unit out of path of falling material. Protect probe from falling material by installing a
shield.
Consider material surface configuration when installing unit.
Tensile load must not exceed probe or vessel rating. On cable units, do not exceed the
tensile strength of the cable at 1900 kg / 4188 lbs.
.
Note: Buildup of material or condensation in the active shield area does not affect
operation.
500 mm
(20") min
500 mm (20") min
50 mm
(2") min
Sensors must be at least 50 mm (2") from the wall or tank bottom and must be 500 mm (20") apart.
50 mm
(2") min
Wall Restriction Multiple Units