SITRANS P310 with HART
12 A5E35075329-01, 05/2015
Installation location requirements
The device may overheat if there is an insufficient supply of air.
• Install the device so that there is sufficient air supply in the room.
• Observe the maximum permissible ambient temperature. Refer to the information in the section "Technical data
Damage to device through penetration of aggressive vapors.
•
Ensure that the device is suitable for the application.
Increased measuring errors.
• Protect the device from direct sunlight.
Make sure that the maximum ambient temperature is not exceeded. Refer to the information in the section Technical data
(Page 34).
The device can be damaged, destroyed, or its functionality impaired through improper mounting.
• Before installing ensure there is no visible damage to the device.
• Make sure that process connectors are clean, and suitable gaskets and glands are used.
• Mount the device using suitable tools. Refer to the information in Technical data (Page 34) for installation torque
Loss of degree of protection
Damage to device if the enclosure is open or not properly closed. The degree of protection specified on the nameplate or in
Chapter "Technical data (Page 34)" is no longer guaranteed.
•
Make sure that the device is securely closed.
Connecting the device (Page 20)