SITRANS P310 with HART
34 A5E35075329-01, 05/2015
Span (continuously adjustable) or
measuring range, maximum operating
pressure (as per 97/23/EC Pressure
Equipment Directive) and maximum test
pressure (as per DIN 16086)
Span Maximum
operating pressure
Maximum test pressure
0.01 … 1 bar
1 … 100 kPa
4 bar
400 kPa
6 bar
600 kPa
0.04 … 4 bar
4 … 400 kPa
7 bar
700 kPa
10 bar
1 MPa
0.16 … 16 bar
16 ... 1600 kPa
21 bar
2100 kPa
32 bar
3200 kPa
0.63 ... 63 bar
63 … 6300 kPa
67 bar
6700 kPa
100 bar
10 MPa
1.6 ... 160 bar
0.16 ... 16 MPa
167 bar
16.7 MPa
250 bar
25 MPa
4 ... 400 bar
0.4 … 40 MPa
400 bar
40 MPa
600 bar
60 MPa
7 … 700 bar
0.7 ... 70 MPa
800 bar
80 MPa
800 bar
80 MPa
• Measuring cell with silicone oil filling
0.03 bar a/3 kPa a/0.44 psi a
Between the measuring limits (fully adjustable)
Differential pressure and flow rate input
Differential pressure and flow rate
Span (continuously adjustable) or
measuring range, maximum operating
pressure (as per 97/23/EC pressure
device guideline) and maximum test
pressure (as per DIN 16086)
Span Maximum operating pressure MAWP
1 ... 60 mbar
0.1 … 6 kPa
0.4015 … 24.09 inH
2
O
160 bar
16 MPa
2320 psi
2.5 ... 250 mbar
0.25 … 25 kPa