SITRANS P310 with HART
36 A5E35075329-01, 05/2015
7.3
Operating conditions
Gauge pressure rated conditions
Installation conditions
Ambient conditions
Ambient temperature
Note
Observe the temperature class in hazardous areas.
Measuring cell with silicone oil
filling
-40 … +85 °C (-40 … +185 °F)
Display -30 … +85 °C (-22 … +185 °F)
Storage temperature -50 … +85 °C (-58 … +185 °F)
Climate class
Condensation
Permitted
Degree of protection in
accordance with EN 60529
IP66, IP68
Electromagnetic compatibility
Interference emission and
interference immunity
In accordance with EN 61326 and NAMUR NE 21
Process medium conditions
Process temperature
Measuring cell with silicone oil
filling
-40 … +100 °C (-40+212 °F)
With extension to Zone 0
-20 … +60 °C (-4 … +140 °F)
Rated conditions for differential pressure and flow rate
Installation conditions
Installation instruction
any
Ambient conditions
Ambient temperature
Note
Observe the temperature class in hazardous areas.
Measuring cell with silicone oil
filling
-40 … +85 °C (-40 … +185 °F)
3000 kPa (435 psi)
measuring cell
-20 … +85 °C (-4 … +185 °F)
For flow: -20 … +85 °C (-4 … +185 °F)
Display
-30 … +85 °C (-22 … +185 °F)
Storage temperature -50 … +85 °C (-58 … +185 °F)
Climate class
Condensation Permitted
Degree of protection in
accordance with EN 60529
IP66, IP68
Electromagnetic compatibility
Interference emission and
interference immunity
In accordance with EN 61326 and NAMUR NE 21
Process medium conditions
Process temperature
Measuring cell with silicone oil
filling
-40 … +100 °C (-40 … +212 °F)
3000 kPa (435 psi)
measuring cell
-20 … +85 °C (-4 … +185 °F)