● Fasten the capillary line such that there are no vibrations.
● Permissible height differences:
– When installing the pressure measuring device above the measuring point, keep the following in mind: the height
difference of H
1max.
for remote seal measuring systems with silicone, glycerin or paraffin oil filling. = 7 m must not be
exceeded.
– If halocarbon oil is used as the filling liquid, this maximum height difference is only H
1max.
= 4 m, see installation types
A and B.
If negative overpressure is observed during measurements, reduce the permissible height difference accordingly.
Installation type for gauge pressure and level measurements (open containers)
Pressure transmitter above the measuring point
MA
= ρ
FL
* g * H
U
- ρ
oil
* g * H
1
ME
= ρ
FL
* g * H
O
- ρ
oil
* g * H
1
Pressure transmitter belo
w the measuring point
MA
= ρ
FL
* g * H
U
+ ρ
oil
* g * H
1
ME
= ρ
FL
* g * H
O
+ ρ
oil
* g * H
1
H
1
≤ 7 m (23 ft); with halocarbon oil as the filling liquid, only H
1
≤ 4 m(13.1 ft)
Density of the process medium in the container
Density of the filling oil in the capillary line of the remote seal
Acceleration due to gravity
Distance between the container flange and the pressure transmitter