Siemens
A6V12681520_enUS_a
Smart Infrastructure
02/09/2023
Power supply
Operating
voltage
SSD161S.05DU,
SSD161S.25DU
AC 24 V (± 15 %) or DC 24 V (± 20 %)
SSD131.29U
AC 24 V (± 20 %)
Frequency
50/60 Hz
Power
consumption
SSD161S.05DU
Normal Operation: 3.5 VA (AC); 1.5 W (DC)
SSD161S.25DU
Normal Operation: 3.5 VA (AC); 1.5 W (DC)
Peak (Ultra cap recharge): 8 VA (AC); 4 W (DC)
SSD131.29U
Normal Operation: 3 VA (AC); 1.5 W (DC)
Peak (Ultra cap recharge): 6 VA (AC); 4 W (DC)
Primary fuse or
breaker rating
External, 2 A quick blow
Signal input
Control signal
Modulating: DC 0...10 V to Y
Floating: AC 24 V to Y1 or Y2
Input impedance
100 kOhm
Parallel operation (number
of actuators)
Max. 10 modulating or 24 floating actuators
1)
Signal output
Feedback signal (modulating actuators only)
DC 0...10 V
Max. output current
1 mA
Max. output voltage
-
Resolution
1:100
Operating data
Position with de-energized contact Y
See "Technical design [ 2]
Running speed (time for 5.5 mm)
SSD161S.05DU, SSD161S.25DU: 5 s/mm ± 25 % (27.5
s ± 25 %)
SSD131.29U: 16 s/mm ± 25 % (88 s ± 25 %)
Positioning force
67 lbf (300 N )
Stroke
0.05 to 0.25 inch (1.2…6.5 mm )
Permissible temperature of medium in the connected
valve
34 to 248°F (1…120)