3-21
The Function Menu displays commonly used control functions described below
in Table 3-6.
Table 3-6. Function Menu Options
Function Description Access
Level
Manual Evacuation Activates the Manual Evacuation
operation (NACs activate and
Fire Alarm LED flashes until
<
ACK> is pressed.
3 or 4
City Circuit Disconnect Disconnects the City Circuit. 3 or 4
Control Point Bypass Bypasses the following Control
Points:
On until Silence signal
Resettable signals
AHU outputs
3 or 4
Elevator Bypass Bypasses the Elevator Recall. 3 or 4
Doorholder Bypass Bypasses the Doorholder
operation.
3 or 4
Lamp Test Illuminates all LEDs and all LCD
segments on the display.
1 4
Table 3-7 describes the steps to access Manual Evacuation.
Table 3-7. Manual Evacuation
Step Action LCD Display
1.
Log In to the 4005 at Access Level 3 or 4.
2.
From the High-Level Status display, press
<
Function>.
3.
Press <ó
Next> or < Previous> to scroll through
the menu until [
Manual Evacuation] is displayed and
then press <
Enter>.
4.
Press <ó
Next> or < Previous> to select [On] or
[
Off] and then press <Enter>.
5.
Press <
Enter> again to confirm your choice.
6.
If [
On] is selected in step 4, the display shown at
the right appears and the Manual Evacuation
begins.
To turn OFF Manual Evacuation: Repeat steps 1 5 above then press
<
SYSTEM RESET>
Continued on next page
Function Menu
Overview
Manual Evacuation
6<67(0,61250$/
SP 7XH-XO
6<67(0,61250$/
&RQWURO>0DQXDO(YDFXDWLRQ@
0DQXDO(YDFXDWLRQ
&RQWURO>2II@ 6WDWXV 2))
0DQXDO(YDFXDWLRQ
)LUH3RLQW $/$50
Technical Manuals Online! - http://www.tech-man.com