Page 17 579-1019 Rev M
4009 IDNAC Repeater Installation Instructions
Compatible devices
Software requirements
In order to properly program the Repeater the computer must use ES Panel FACP System Firmware version 1.04 or later. Consult the ES Panel
Programmer’s Manual (574-849) for more information.
Adding the Repeater to the ES Programmer
The Repeater is programmed through the EPS Point Editing tab. To program the Repeater, complete the following steps:
1. Open or create a job in the ES Programmer.
2. Click the Hardware tab.
3. Double-click the EPS module connected to the Repeater to open the Properties window.
4. Click the Point Editing tab.
5. From the Select Device list, select REPEATER
100%
Fig 17: the Repeater
Setting the card properties
The Card Properties tab has the following input options:
Custom Label: Enter a label that describes the card function, location, or other information.
Alternate Label: Enter an alternative description of the card.
Current Draw (Amps): This option specifies the current drawn by the device. The current draw is based on the device PID. To open the Power table
and select the device, press the F11 key. When the correct device is selected, and the quantity entered the correct power rating for this device is
displayed.
Primary Action: Assign a Primary state Action Message to use for the NAC circuit. Select the action message from the list of default and user
defined messages.
Trouble Action: Assign a Trouble state Action Message to use for the NAC.
Depleted Battery Cutout: If this check box is selected the Repeater shuts off after detecting a depleted battery condition when no AC power is
present. This option is clear by default.
Repeater Options: Select the option from the list that corresponds to the Repeater wiring style.
- Class B Spur for Local Class B wiring
- Class A Spur for Local Class A Loop wiring
- Class A Loop for Extended Class A Loop wiring