Page 4 579-1019 Rev M
4009 IDNAC Repeater Installation Instructions
Installing the batteries
The Repeater cabinet is built to accommodate two 12.7 AH batteries.
To safely install the batteries in the Repeater Cabinet using the battery harness, complete the following steps:
1. Place both batteries to the left side on the bottom of the cabinet.
2. Connect the positive terminal of the left battery to the positive battery input on the Repeater using the red cable.
3. Connect the negative terminal of the right battery to the negative battery input on the Repeater using the black cable.
4. Connect the two remaining battery terminals using the white jumper cable, to join the two batteries.
Negative
Jumper
Positive
Battery Input
100%
Fig 4: Installing the batteries