3-14
 
Use the following to wire the QuickConnect smoke sensors. 
CAUTION:  Do not loop wire under terminals.  Break wire runs to provide 
supervision. 
 
(SEE 
NOTE 1)
4098-9788
FROM 
PANEL
-IDNet
+IDNet
SHIELD IS 
OPTIONAL 
(SEE NOTE 3)
SHIELD
SHIELD
SHIELD
TO OTHER IDNet
     DEVICES
  (SEE NOTE 2)
-IDNet
+IDNet
4098-9788
4098-9788
 
 
Figure 3-12.  QuickConnect Sensor Connections 
FigureTag FD4-709-10  
Notes: 
1.  4098-9757 QuickConnect sensor uses the 4098-9788 base. 
2.  Maximum quantity of devices per IDNet circuit is 250 for the 4010, 4100U and 4100ES (with 
4190-3106) panel.   
3.  If shield is used, twist shield wires together and cap with wire nut.  Shield should be insulated 
from electrical box. 
 
 
4098 TrueAlarm QuickConnect Smoke Sensors, 
Continued 
Wiring