5-10
Table 5-5. Sensor’s Analog Value
Trouble Indications,
Continued
The panel will automatically indicate when a sensor is out of its sensitivity calibration. If
the sensor has an analog value below what is listed in the table, the sensor is within its
sensitivity setting.
Sensor’s Analog Value
Type Almost Dirty Dirty Excessively Dirty
Photo 115 120 135
Ion 135 140 155
To view a Sensor’s analog value, refer to your panels operating instructions