Communication Modules (not available with 4100-9611)
Dual RS-232 Interface, mounts in Slot 3 or Slot 2
Master Clock Interface Module with one standard RS-232 port (see S4100-0033)
Panel Mounted Printer (not available with 4100-9611, refer to document S4100-0032 for additional detail)
Panel Mount Thermal Printhead Printer, supplied with one roll of paper; requires 3 expansion slots
Replacement Paper for 4100-1293 Printer, one roll
Power Supplies and Accessories
Remote Power Supply (RPS); 9 A power supply
with battery charger; Canadian model has low
battery cutout; required for 4100-9610, not
available with 4100-9611
Box Interconnection Harness Kit; order one for each close-nippled cabinet; also used if power is supplied from host
fire alarm control panel
Power Distribution Modules
Power Distribution Module (PDM);
select per system voltage
Required for 4100-9610, select one per box or
cabinet rack; not applicable for 4100-9611
Miscellaneous Accessories
Expansion Bay Hardware, order one for each expansion bay (unless included with selected option)
Single blank 2” display cover, order as required (8 fill a bay front); 2 max. between LED/switch modules
Termination and Address Label Kit (for module marking); provides additional labels for field installed modules
Terminal Block Utility Module; provides 2, 16 position terminal blocks mounted on 4” x 5” single block size, capable of
up to 12 AWG wire (3.31 mm
2
)
Door Tamper Switch (connects to Transponder Interface Module)
Kits of 8 LEDs; order as required for 4100-1276/1277/1300 modules
Remote Power Supplies (RPS)
4 A maximum @ 102 to 132 VAC, 60 Hz
2 A maximum @ 204 to 264 VAC, 50/60 Hz;
separate taps for 220/230/240 VAC
Power Supply Output Ratings for the Remote Power Supply (RPS)
Total Power Supply Output Rating
9 A total @ nominal 28 VDC, including module currents
and auxiliary power outputs
Output switches to
battery backup
during mains AC
failure or brownout
conditions
NACs Programmed for Auxiliary Power
2 A maximum per NAC,
5 A maximum total
Battery Charger, Remote Power Supply (RPS) (sealed lead-acid batteries)
UL listed for battery charging of 6.2 Ah up to 110 Ah (batteries larger than 50 Ah
require a remote battery cabinet); ULC listed for charging up to 50 Ah batteries
Charger characteristics and performance
Temperature compensated, dual rate, recharges depleted batteries within 48
hours per UL Standard 864, to 70% capacity in 12 hours per ULC Standard S527
Operating Temperature Range
32° to 120°F (0° to 49° C)
Up to 93% RH, non-condensing @ 90° F (32° C) maximum