120 VAC Models 3.5 A maximum @ 102 to 132 VAC, 60 Hz
Input Power [System (SPS); Expansion (XPS);
Remote (RPS); TrueAlert (TPS) and 100 W
amplifiers]
220-240 VAC Models
1.75 A maximum @ 204 to 264 VAC, 50/60 Hz;
separate taps for 220/230/240 VAC
Total Power Supply
Output Rating
9 A total @ nominal 28 VDC, including module currents and
auxiliary power outputs
Auxiliary Power Tap 2 A maximum @ nominal 28 VDC
Power Supply Output
Ratings (System,
Expansion, and Remote
Power Supplies)
NACs Programmed
for Auxiliary Power
2 A maximum per NAC, 5 A maximum @ nominal 28 VDC
Output switches to
battery backup
during mains AC
failure or brownout
conditions
Battery capacity range
6.2 Ah to 50 Ah; selectable via programming for batteries below 18 Ah; the SPS is UL
listed for up to 110 Ah battery charging for remotely located batteries
Battery Charger
(System and Remote
Power Supply)
Charger characteristics
and performance
Temperature compensated, dual rate, recharges depleted batteries within 48 hours per
UL Standard 864, to 70% capacity in 12 hours per ULC Standard S527
Operating Temp. Range 32° to 120°F (0° to 49° C)
Environmental
Operating Humidity Range Up to 93% RH, non-condensing @ 90° F (32° C) maximum
Model Description
4100-6034 Door Tamper Switch with built-in addressable IDNet IAM, one per cabinet assembly if required
4100-2320 Audio Bay-to-Bay Interconnection Harness Kit; order one for each audio bay addition
4100-0637 Audio Box Interconnection Harness Kit; order one for each close-nippled audio cabinet
4100-9835 Termination and Address Label Kit (for module marking); provides additional labels for field installed modules
4100-1293 Panel Mount Thermal Printhead Printer, supplied with one roll of paper; requires 3 Slots; see S4100-0032 for details
4190-9803 Replacement Paper for 4100-1293 Printer, one roll
4100-6045 Coded Manual Station Decoder Module; 3 Slot module; 85 mA supervisory, 163 mA alarm; see S4100-0018 for details
4100-6048 VESDA
®
Air Aspiration Interface; 1 Slot module; 132 mA supervisory or alarm, see S4100-0026 for details
Model* Description Model* Description Model* Description
4100-5005 8 Zone IDC, Class B 4100-3101 250 Point IDNet Module 4100-3202 4 DPDT Relays w/feedback, 10 A
4100-5015 8 Zone IDC, Class A 4100-3102 127 Point MAPNET II
®
Module 4100-3204 4 DPDT Relays w/feedback, 2 A
* See S4100-0031 for details 4100-3103 IDNet/MAPNET II Quad Isolator 4100-3206 8 SPDT Relays, 3 A
Model Description
4100-1279 Single blank 2” display cover; order as required (8 fill a bay front); two max. in a row between LED/switch modules
4100-2210 Appliqué, Canadian French, 4100U Fire Control
4100-2300 Expansion Bay Hardware, order for each expansion bay (unless included with selected option)
4100-0636 Box Interconnection Harness Kit; order one for each close-nippled cabinet
4100-0632 Terminal Block Module; 2, 16 position terminal blocks mounted on 4” x 5” single block size, for up to 12 AWG wire (3.31 mm
2
)
7 S4100-0036-4 10/2003
Slot 1 Slot 8Slot 7Slot 6Slot 5Slot 4Slot 3Slot 2
Expansion Bay Chassis
Block A
Block B
Block C
Block D
Block E
Block F
Block G
Block H
Size Definitions: Block = 4” W x 5” H (102 mm x 127 mm) card area
Slot = 2” W x 8” H (51 mm x 203 mm) motherboard with daughter card
General Specifications
Expansion Bay Module Loading Reference (exact locations are provided with shipped product)
Description Mounting
Terminal Block Module 4” x 5”, 1 block
Style 4 Physical Bridge 2”, 1 slot
Style 7 Physical Bridge 4”, 2 slots
System, Remote, or TrueAlert
Power Supply
Blocks E, F, G & H
ONLY
Expansion Power Supply Blocks G & H ONLY
Audio Controller Modules Blocks A & B
Flex-35 Amplifiers, 2 max/bay*
Blocks E & F; C & D; or
A & B
Flex-50 Amplifiers, 2 max/bay* Blocks E & F or C & D
100 W Amplifiers, 1 max/bay Blocks E, F, G & H
100 W Backup Amplifiers, 1 max.
per bay with primary amplifier
Blocks A, B, C & D
Master Telephone Module Blocks A & B
Master Microphone Module (do
not mount next to telephone)
Two vertical Blocks,
any location
Telephone Module 1 Block
Operator LED/Switch Modules 1 Slot
* NOTE: When mounting dual Flex amplifiers on an
expansion bay, special mounting rules apply.
NDU with VCC, Additional Options
NDU or NDU with VCC Additional Options