SmartPump Startup - 23
1. Start
the pump by pressing the
Start Fill button.
2. The
pump
will start and empty
the spill basin. A full basin
should take about 20 seconds to
empty.
3. Stop the pump when the basin is
empty by pressing the Stop Fill
button.
You must purge the pump of air on
initial startup or whenever as has
entered the pump system.
1. Open the Smartpump inlet and
outlet valve to flood the system.
(See Pump Inlet Valve
and
Pump
Outlet Valve
)
2. Open the air purge valve located at
the pump discharge, then close valve.
(See Air Purge Valve)
The pump should now be purged of
air.
DRAINING THE SPILL CONTAINMENT BASIN
PURGING THE PUMP
Pump Inlet Valve
Pump Outlet Valve
Air Purge Valve
APPENDIX C - SMARTPUMP STARTUP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex Full-Size Fuelport and is the answer not in the manual?