FuelPort Operating Instructions - 5
Flush Mounting:
To install the FuelPort into a wall, prepare an opening matching the
dimensions of the FuelPort and attach it via the pre drilled mounting
flange. Verify that the wall and mounting hardware are sufficient to
support the FuelPort's weight. Simplex is not responsible for damage
occurring as a result of insufficient support.
Mounting Full-Sized FuelPort to Floor:
The Full-Sized FuelPort can be secured to a wall, a floor or both using
the pre drilled mounting flanges running the height and length of the
cabinet.
Verify that the surface you are mounting the Full-Sized FuelPort to and
the mounting hardware are sufficient to support the FuelPort's weight.
Simplex is not responsible for damages occurring as a result of
insufficient support.
1. Connect ground cable
2. Unlock FuelPort and open door
3. Connect delivery hose to hose coupling
4. Open valve on truck and valve in FuelPort
5. Start fill pump
6. Stop fill pump when tank is full or as needed
7. Close truck valve and valve in FuelPort
8. Disconnect delivery hose from hose coupling
9. Close and lock FuelPort door
10. Disconnect ground cable
II-B. OPERATING INSTRUCTIONS