38
The administrator can configure security settings, such as lockout delay, number of retries for
logging in, and IP address blocking.
To customize the security settings, click the Security Settings item on the Administration menu.
Then follow the instructions below.
Enter or select the required security settings.
Automatic Lockout Delay. The Lockout Delay period is the amount of time the SafeLINC FPII
can remain idle before logging the user out and returning the host FACP to the lowest access level
(3-30 minutes; default is 10 minutes).
Note: The SafeLINC FPII returns to the host FACP at the lowest login level after 10
minutes of inactivity, or when the user logs out or is automatically logged out.
Login Retries. Specify the number of incorrect logins (1-20 times; default is 3 times) allowed
before the SafeLINC FPII enters lockout. (All users will be unable to log in during lockout.)
SafeLINC FPII Lockout Duration. Specify the amount of time each lockout will last
(0-24 hours; default is 1 hour).
Note: If an event occurs while the SafeLINC FPII is in the lockout state, the lockout
duration expires upon detecting the event that allows users to log in.
Local Configuration Options. These options specify whether you must configure the SafeLINC
FPII on the same sub-domain on which the SafeLINC FPII resides, or on any domain. For
example, if the SafeLINC FPII is at 192.168.0.1 and you are accessing the SafeLINC FPII from
193.168.0.2 with the “Local” option enabled, you would not be able to modify the IP blocking
features. The same rule applies to Email and User Account options. To disable the “Local”
option, you must access the SafeLINC FPII on the same sub-domain (for example: 192.168.0.4 is
on the same sub-domain as 192.168.0.1).
Configure IP blocking locally.
Configure email accounts locally.
Configure user accounts locally.
Network Status Check. Specify a time interval (in minutes) for when the SafeLINC FPII checks
for the presence of its configured network gateway. (With 30 minutes being the default interval,
you can change the interval anywhere from 0 minutes to 4 hours. Entering 0 minutes disables this
feature.)
Although this feature does not guarantee that the entire network is operational, it does confirm that
the SafeLINC FPII can communicate on the network.