ultiFlame DF-TV7 Page 14 / 56 NOSP16358-03 [04/2016]
3. PERFORMANCES
3.1. Sensitivity
3.1.1. F
ire class
Classification according to §5.5.3 –NF EN 54-10 (2006), (ethanol and n-heptane fires)
DF-TV7-XVA0 ET DF-TV7-XTA0
Sensitivity
Time delay
50%
75%
100%
Min
Class 2
Class 1
Class 1
Max (20 sec)
Class 2
Class 2
Class 1
DF-TV7-XTB0
Class 1
f
or any combinations of sensitivity and time delay settings.
3.1.2. Fire range of detection
Detection range for a standard 1 square foot (0.33 x 0.33m) fire except where stated.
XTB0
(IR
3
Long range)
XTA0
(IR
3
–Standard range)
XVA0
(UVIR²)
Sensitivity /
time delay
75 % / 5 sec
(Fact. Setting)
100 % / 5 sec
50 % / 5 sec
100% / 5 sec
(Fact. Setting)
100 % / 2 sec
(Fact. Setting)
Ethyl alcohol
37 m (122
ft.
)
50m (164
)
12 m (40
ft.
)
25m (82
)
25m (82 ft.)
Methanol
*
36
m (120
)
48 m (160
ft.
)
12m (40
)
30 m (100
)
19 m (62
)
Diesel
**
37 m (122
ft.
)
50 m (164
)
12 m (40
ft.
)
25m (82
)
30m
(100 ft.)
Gasoline
**
49 m (161
ft.
)
65 m (213
)
16 m (52
ft.
)
32m (105
)
35m (115 ft.)
JP4 (2x2 ft²)
*
55 m (180
)
73 m (239
ft.
)
21 m (70
)
42 m (138
ft.
)
55 m
(180 ft)
N
-
heptane
*
65 m (215
)
80 m (265
ft.
)
27 m (90
)
54 m (177
ft.
)
45m
(147 ft)
*** Methane
45
m (1
47
ft.)
60 m (200 ft.)
15 m (49
ft)
30 m (100 ft.)
35m (115 ft.)
Propane
(10in.)*
6.4 m (252in.)
8.5 m (336 in.)
2.4 m (95 in.)
4.8 m (190in.)
4.8 m (190 in.)
(*) Tested according to the FM 3260 standard
(**) Other measurements (
Italic:
calculated Extrapolation)
(***) Measured on a 0.17x0.17 size fire with a plume height of about 0.8 m
Bold = experimental measures, italic =extrapolations