ultiFlame DF-TV7 Page 36 / 56 NOSP16358-03 [04/2016]
6.7. Information menu [INFO]
The information menu contains all information concerning the identity and settings of the
detector. The first screen gives the detector’s reference and its serial number.
6.7.1. [IDEN]tity submenu
Presentation of:
detector operation mode (UV/2IR, UV, IR(2IR or 3IR))
Sensor sensitivity (50, 75, 100%)
Alarm time delay (seconds)
Sub-menus present the board software version and the power supply voltage.
6.7.2. [OUT]put submenu
Presentation of:
Current protocol (0-22 mA or 4-20 mA)
Normal state of the relays (normally open or normally closed)
Conditions of relays activation
Relays can be set with a level 2 access.
6.7.3. [STAT]e Information sub-menu
Presentation of:
Alarms history
Alarm activation
Faults list (use F1 key to scroll faults)
Alarm count since last reset
Failed optical self-test count since last reset
[ALRM] Alarm screen
6.7.3.1.
Allows Alarms history display.
[FLT.] Fault screen
6.7.3.2.
Displays a list of eventual faults (press F1 key to scroll through the list)
Network Screen Switch
6.7.3.3.
This menu and its sub-menus are used for the network detector settings. For any further
details, please refer to the Syntel system operating manuals.
MODE SCREEN
The first line shows the operating mode of the sensor in the network (logic link test/out of
o
rder/emulation).
The second line shows if the network part of the detector is “operating” or “out of order”. For
any further details, please refer to the Syntel system operating manuals.
NETWORK SCREEN: ALIM
Information displayed:
V
oltage A: ON / OFF
Voltage B: ON / OFF
For any further details, please refer to the Syntel system operating manuals