M
ultiFlame DF-TV7 Page 16 / 56 NOSP16358-03 [04/2016]
3.3. False alarm immunity (FM 3260)
Distance
m (ft.)
XTB0 (IR3)
Long range
XTA0 (IR3)
Standard
range
XVA0 (UVIR²)
Modulated /
Steady
75 % / 5 sec
(fact. setting)
100% / 5 sec
(fact. setting)
100 % / 2 sec
(fact. setting)
Arc welding, steady,
#7014, 3/16 in,
190A
3.6 / 3.6 (12/12) No False Alarm No False Alarm
No false Alarm
7.6 / 7.6 (25/25)
1.5 kW heater
3.0 / 1.8 (10/6) No False Alarm No False Alarm No False Alarm
100 W incandescent
lamp
0.9 / 0.9 (3/3) No False Alarm No False Alarm No False Alarm
Two 40 W
fluorescent lamps
0.9 / 0.9 (3/3) No False Alarm No False Alarm No False Alarm
100 W halogen
lamp
2.4 / 2.4 (8/8) No False Alarm No False Alarm No False Alarm