FAILURES TO OPERATE DISPLAY
While operating, in case of a problem, a fault no. is displayed sometimes
transiently in the form Er.
.xx
. These faults are stored.
The card has a 10 faults store stack accessible in the PARA mode in the
Err parameter.
The fault stack can be cleared after analysis.
How to read the 10 stored faults :
Scroll the menus by successively pressing
Select PARA by pressing
.
Press successively to go to Err : validate
The screen displays the last stored fault.
Example of display : 0 = 8
Most recently stored fault 0 Error 8
Press
=> display : 1 = xx (previous fault)
Continue to press => display : 9 = xx (oldest stored fault)
(When is pressed, the fault stock contents are displayed in the reverse
order.)
How to clear the stored fault stack :
Scroll the menus by successively pressing
Select PARA
by pressing .
Press successively to go to Err : validate
The screen displays the last stored fault.
Press until
EFFA
is displayed, and then validate
The fault stack is cleared
Return to the Err display
To quit the PARA
mode, simultaneously press and