SMA America, LLC 19 Parameter Lists
Technical description SI4548_6048-US-TB_en-13 157
19 Parameter Lists
Only parameters in the menu branches "200 Settings" and "500 Operation" can be changed.
All other values are only shown on the display of the SI 4548-US-10/6048-US-10. All menu items
that can only be changed by the installer using a password are shaded in gray in the following tables.
19.1 Display Values
19.1.1 Inverter Meters (110#)
111# Inverter Total Meters
#112 Inverter Device Meters
Menu structure depends on system configuration
Depending on the set system configuration, individual menu items may be missing.
Interference during operation due to incorrect parameter settings
Use caution when setting parameters. Incorrect settings can lead to faulty operation of the
inverter. Take note of the original values of all parameters that you change.
No. Name Description
01 TotInvPwrAt Total active power of the inverters (cluster) in kW
02 TotInvCur Total current of the inverters (cluster) in A
03 TotInvPwrRt Total reactive power of the inverters (cluster) in kVAr
No. Name Description Value clear text
(No.)
Explanation
01 InvOpStt Operating state of
the Sunny Island
Standby (2) Standby
Run (3) Operation
Run
(4)/EmCharge
Emergency charge mode
Error (5) Error
Startup (1) Transfer standby > operation
02 InvPwrAt Active power
Sunny Island in kW
03 InvVtg Voltage of the
Sunny Island in V