SMA America, LLC 19 Parameter Lists
Technical description SI4548_6048-US-TB_en-13 167
19.2.2 Battery Settings (220#)
221# Battery Property
No. Name Description Value Explanation Default
value
01 BatTyp Battery type VRLA Lead-acid battery
with immobilized
electrolyte in gel or
AGM (Absorbent
Glass Mat
Separator)
VRLA
FLA Valve-regulated
lead-acid battery
with liquid electrolyte
NiCd Nickel-cadmium
battery
02 BatCpyNom Nominal battery
capacity
(E:C10/U:C20)
100 Ah
03 BatVtgNom Nominal battery
voltage
VRLA 48 V
FLA 48 V
NiCd 45.6 V
04 BatTmpMax Maximum battery
temperature
104°F to 122°F
(40°C to 50°C)
113°F
(45°C)
05 BatTmpStr Battery start
temperature
following stop due
to overtemperature
32°F to 104°F
(0°C to 40°C)
"BatTmpMax"
104°F
(40°C)
06 BatWirRes Power resistor of
the battery
connection in
mOhm
0 mOhm to
50 mOhm
07 BatFanTmpStr Starting
temperature for the
"BatFan" function
104°F
(40°C)

Table of Contents