SMA Solar Technology America LLC 19 Parameter Lists
Operating Manual SI4548-6048-US-BE-en-21 171
#224 Battery Silent Mode
225# Battery Current Sensor
No. Name Description Value Explanation Default
value
01 SilentEna Silent mode on utility
grid
Disable Disable Disable
Enable Enable
02 SilentTmFlo Maximum time for float
charge until transfer
into silent mode
1 h to 48 h 3 h
03 SilentTmMax Maximum time for
silent until transfer into
float
1 h to 168 h 12 h
No. Name Description Value Explanation Default
value
01 BatCurSnsTyp Battery current sensor
type
None No sensor is
connected.
None
60 mV Battery current
sensor 60 mV
50 mV Battery current
sensor 50 mV
02 BatCurGain60 External battery current
sensor type (60 mV
type)
0 A to
1,000 A
100 A/
60 mV
03 BatCurGain50 External battery current
sensor type (50 mV
type)
0 A to
1,000 A
100 A/
50 mV
04 BatCurAutoCal Automatic calibration
of external battery
current sensor
Start Start automatic
calibration