236# CHP Control (Combined Heat and Power)
237# CHP Start
No. Name Description Value Explanation Default
value
01 ChpOpTmMin Minimum run time of
CHP plant
60 min
02 ChpStpTmMin Minimum stop time of
CHP plant
10 min
03 ChpPwrMax Maximum power of
CHP plant
5 kW
04 ChpPwrMin Minimum power of
CHP plant
2 kW
05 ChpFrqPwrMax Maximum frequency of
CHP plant
51 Hz
06 ChpFrqPwrMin Minimum frequency of
CHP plant
52 Hz
07 ChpFrqOff 53 Hz
No. Name Description Value Explanation Default
value
01 ChpSocTm1Str SOC limit for switching
on CHP plant for time 1
40%
02 ChpSocTm1Stp Switch off SOC limit for
CHP plant for time 1
80%
03 ChpSocTm2Str SOC limit for switching
on CHP plant for time 2
40%
04 ChpSocTm2Stp Switch off SOC limit for
CHP plant for time 2
80%
05 ChpTm1Str Time 1 for CHP plant
request in hours,
minutes and seconds
Start: time 1, end: time
2
06 ChpTm2Str Time 2 for CHP plant
request in hours,
minutes and seconds
Start: time 2, end: time
1