7 Manually Controlling the Generator SMA Solar Technology AG
46 SI80H-BE-BEN120810 Operating Manual
7.3 Starting the Generator without Autostart Function
Requirement:
The generator is not controlled with GenMan.
1. Start the generator (see manufacturer's instructions).
2. Close the switch-disconnector between generator and off-grid inverter.
After the warm-up period, the off-grid inverter switches the stand-alone grid to the generator.
7.4 Stopping the Generator without Autostart Function
Requirement:
The generator is not controlled with GenMan.
1. Open the switch-disconnector between the generator and off-grid inverter. That prevents the
generator being driven by AC sources in the stand-alone grid.
2. Stop the generator (see manufacturer's instructions).
The generator is stopped. After the cool-down time and the minimum stop time, you can use the
generator as an external energy source again.