SMA Solar Technology AG 8 Disconnecting the Off-Grid Inverter from Voltage Sources
Operating Manual SI80H-BE-BEN120810 47
8 Disconnecting the Off-Grid Inverter from Voltage
Sources
1. Switch off the off-grid system (see Section 5.4).
2. Disconnect the miniature circuit-breaker and the switch-disconnectors in the sub-distributions and
secure against reconnection.
3. Open the switch-disconnector of the BatFuse and secure against reconnection.
6. If you are a skilled person, loosen all the screws of the enclosure lid and remove the lid.
7. Ensure that the DC terminal is disconnected from voltage sources.
8. Ensure that the terminals AC1 Loads/SunnyBoys and AC2 Gen/Grid are disconnected from
voltage sources.
9. Earth and short-circuit the AC conductors.
10. Cover or safeguard any adjacent live components.
4.
Danger to life due to high voltages
If you are not a skilled person, inform a skilled person.
Steps 5 to 10 may only be performed by skilled persons.
5.
Electrostatic discharges can damage the off-grid inverter.
The components inside the inverter can be destroyed by electrostatic discharge.
Earth yourself before touching any components.

Table of Contents