10 Troubleshooting SMA Solar Technology AG
64 SI80H-BE-BEN120810 Operating Manual
Charging the Battery
1. Switch off all loads.
2. Activate or deactivate all miniature circuit-breakers and/or fuse-switch-disconnectors for energy
sources.
3. Quickly connect the switch-disconnector of the BatFuse and close the BatFuse
(see the installation manual of the BatFuse).
4. Start the generator.
5. Switch the off-grid inverter on (see Section 5.1).
6. If the Sunny Remote Control shows <Init System> , press and hold the button.
☑ The Sunny Remote Control shows the QCG.
7. Select menu Emerg Charge and press the button.
8. Confirm with Y.
☑ The Sunny Remote Control shows the
ExtCurMax parameter.
9. Set the AC current of the connected generator and press the button.
10. Confirm the AC current with Y.
11. Turn the button to the right and confirm the message
Emerg. Charg Mode Start?.