13 Technical Data
SMA Solar Technology AG
Operating manual STP50-40-BE-en-15 107
Operating range at AC power frequency 50Hz 44Hz to 55Hz
Operating range at AC power frequency 60Hz 54Hz to 65Hz
Power factor at rated power 1
Displacement power factor, adjustable 0.0overexcitedto0.0underexcited
Feed-in phases 3
Phase connection 3 (+1)
Surge category in accordance with
IEC62109-1
III
* Depending on the configured country data set
Multifunction relay
Maximum DC switching voltage 30V
Maximum AC switching current 1.0A
Maximum DC switching current 1.0A
Minimum load 0.1W
Minimum electrical endurance when the maxi-
mum switching voltage and maximum switching
current are complied with*
100000 switching cycles
* Corresponds to 20years at 12switching operations per day
Efficiency
Maximum efficiency, η
max
> 98.1%
European weighted efficiency, η
EU
> 97.8%
Protective Devices
DC reverse polarity protection Short-circuit diode
Input-side disconnection point DC Load-Break Switch
DC surge protection Surge arrester type1 and 2 (optional)
AC short-circuit current capability Current control
Grid monitoring SMA Grid Guard 10.0
Maximum overcurrent protection 100A
Ground fault monitoring Insulation monitoring: R
iso
>34kΩ
All-pole sensitive residual-current monitoring unit Available