6 Electrical Connection
SMA Solar Technology AG
Operating manualSTP50-40-BE-en-1536
13. When N is present and connected to the
corresponding terminal, remove the bridge installed
as standard between N and the enclosure ( ). To
do so, unscrew the screw of the terminal N and the
screw of the grounding point ( ) using an Allen
key (AF8, length: 50mm) and remove the bridge
from the inverter.
L1
L2
L3
N
14. Ensure that the correct conductors are assigned to all the terminals.
15. Make sure that all conductors are securely in place.
6.3 Connecting the Network Cables
DANGER
Danger to life due to electric shock in case of overvoltages and if surge
protection is missing
Overvoltages (e.g. in the event of a flash of lightning) can be further conducted into the building
and to other connected devices in the same network via the network cables or other data cables
if there is no surge protection. Touching live parts and cables results in death or lethal injuries due
to electric shock.
Ensure that all devices in the same network are integrated in the existing overvoltage
protection.
When laying the network cable outdoors, ensure that there is suitable surge protection at
the network cable transition from the product outdoors to the network inside the building.
The Ethernet interface of the inverter is classified as "TNV-1" and offers protection against
overvoltages of up to 1.5kV.
Additionally required material (not included in the scope of delivery):
Network cables
Where required: Field-assembly RJ45 connector.