6 Electrical Connection
SMA Solar Technology AG
Operating manual STP50-40-BE-en-15 33
6.2 AC Connection
6.2.1 Requirements for the AC Connection
AC cable requirements as follows:
☐ Conductor type: aluminum and copper wire
☐ External diameter: 35mm to 48mm
☐ Conductor cross-section of grounding conductor: 25mm² to 120mm²
☐ Conductor cross-section of line conductor and neutral conductor: 35mm² to 120mm²
☐ Insulation stripping length: 30mm
☐ Sheath stripping length: 290mm
☐ The cable must be dimensioned in accordance with the local and national directives for the
dimensioning of cables. The requirements for the minimum wire size derive from these
directives. Examples of factors influencing cable dimensioning are: nominal AC current, type of
cable, routing method, cable bundling, ambient temperature and maximum desired line losses
(for calculation of line losses, see the design software "SunnyDesign" from software
version2.0 at www.SMA-Solar.com).
Overview of the required length of the conductor inside the AC connection unit
Figure 10: Interior view of the AC connection unit with dimensions for the conductors (Dimensions in mm)