11 Troubleshooting
SMA Solar Technology AG
Operating manualSTP50-40-BE-en-1586
Event number Message, cause and corrective measures
3801
3802
3803
3805
3806
3807
3808
DC overcurrent > Check generator
Overcurrent at the DC input. The inverter briefly interrupts feed-in operation.
Corrective measures:
If this message is displayed frequently, ensure that the PV array has been
correctly rated and wired.
6002-6412
Self diagnosis > Interference device
The cause must be determined by the Service.
Corrective measures:
Contact Service.
6502
Self-diagnosis > Overtemperature
The inverter has switched off due to excessive temperature.
Corrective measures:
Clean the cooling fins on the rear of the enclosure and the air ducts on
the top using a soft brush.
Ensure that the inverter has sufficient ventilation.
Ensure that the inverter is not exposed to direct solar irradiation.
6512
Minimum operating temperature not reached
The inverter will only recommence grid feed-in once the temperature has
reached at least −25°C.
6603
6604
Self-diagnosis > Overload
The cause must be determined by the Service.
Corrective measures:
Contact Service.
6701
6702
Communication disturbed
Error in the communication processor, the inverter continues feeding in, how-
ever. The cause must be determined by the Service.
Corrective measures:
If this message is displayed frequently, contact the Service.