EasyManua.ls Logo

Smartgen ALC700 SERIES

Smartgen ALC700 SERIES
51 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ALC700 Series Light Tower Set Controller
ALC700 Series Light Tower Set Controller 2018-03-02 Version 1.4 Page 28 of 51
No.
Type
Description
13
Pressure Sensor
Open
When controller detects the oil pressure sensor is open circuit,
it will send shutdown signal and the corresponding alarm
information will be displayed on the LCD.
14
Temp. Sensor
Open
When controller detects the temperature sensor is open circuit,
it will send a shutdown signal and the corresponding alarm
information will be displayed on the LCD.
15
Low Fuel Level
When controller detects the fuel lever is lower than the set
value, it will send shutdown signal and the corresponding
alarm information will be displayed on the LCD.
16
Flexible Sensor
Open
When controller detects the sensor is open circuit, it will send a
shutdown signal and the corresponding alarm information will
be displayed on the LCD. If the sensor name is configured by
users as xxx, then “xxx open” will be displayed on the LCD.
17
Flexible Sensor
High
When controller detects the sensor value is higher than the
maximum set value, it will send shutdown signal and the
corresponding alarm information will be displayed on the LCD.
If the sensor name is configured by users as xxx, then “xxx
high” will be displayed on the LCD.
18
Flexible Sensor
Low
When controller detects the sensor value is lower than the
minimum set value, it will send shutdown signal and the
corresponding alarm information will be displayed on the LCD.
If the sensor name is configured by users as xxx, then “xxx
low” will be displayed on the LCD.
19
Aux. input 1-4
When the controller detects auxiliary input ports 1-4 shutdown
alarms, it will send shutdown alarm signal and the
corresponding alarm information will be displayed on the LCD.
If the input port name is configured by users as xxx, then “xxx
shutdown” will be displayed on the LCD.
NOTE: The shutdown alarm types of Aux. input are active only when they are configured
by users.