ALC700 Series Light Tower Set Controller
ALC700 Series Light Tower Set Controller 2018-03-02 Version 1.4 Page 36 of 51
8.2 ENABLE DEFINITION OF PROGRAMMABLE OUTPUT PORT 1-4
No.
Type
Description
0
Not Used
1
Air Flap
Action when over speed shutdown and emergence
stop. It also can close the air inflow to stop the engine
as soon as possible.
2
Audible Alarm
Action when common alarm output and the output
delay can be set by users.
3
Battery High Volts
Action when battery’s over voltage warning alarm.
4
Battery Low Volts
Action when battery’s under voltage warning alarm.
5
Reserved
6
Reserved
7
Reserved
8
Start Relay
Action when genset is cranking and disconnect when
start successfully.
9
Fuel Relay
Action when genset is cranking and disconnect in fail
to stop delay.
10
Auto Start Mode
In auto start mode, action when start and disconnect
when stop.
11
Charge Alt Fail
Action when charge failure warning alarms.
12
Reserved
13
Reserved
14
Reserved
15
Reserved
16
Over/Under Freq. Shut
Action when generator over/under frequency
shutdown.
17
Over/Under Freq. Warn
Action when generator over/under frequency warn.
18
Over/Under Volt. Shut
Action when generator over/under voltage shutdown.
19
Over/Under Volt. Warn
Action when generator over/under voltage warn.
20
Common Alarm
Action when genset common warning, common
shutdown, common trips alarm.
21
Common Trip Alarm
Action when common trips alarm.
22
Common Shutdown
Action when common shutdown alarm.
23
Common Warn Alarm
Action when common warning alarm.
24
High Temp Warn
Action when hi-temperature warning. (engine
temperature sensor)
25
High Temp Shutdown
Action when hi-temperature shutdown alarm (engine
temperature sensor).
26
Cooling Timer in Progress
Action when cooling delay is in ongoing.
27
Reserved
28
Aux Input 1 Active
Action when input port 1 is active.
29
Aux Input 2 Active
Action when input port 2 is active
30
Aux Input 3 Active
Action when input port 3 is active
31
Aux Input 4 Active
Action when input port 4 is active