HGM6100N Series Genset Controller User Manual Page 26 of 47
No.
Items
Description
21
ECU Warning
Indicate ECU sends a warning signal.
22
ECU Shutdown
Indicate ECU sends a shutdown signal.
23
ECU Comm. Failure
Indicate controller can’t communicate with ECU.
24
Speed Raise Pulse
Raising speed time is output while the unit entering into
high-speed warming up.
25
Speed Drop Pulse
Dropping speed time is output while the unit entering into stop
idling.
26
Oil Pump Control
This function only suits for HGM6100CAN with engine type
Yuchai-LMB. When unit is standby, pump control output per 30
minutes. If oil pressure is above 100kPa or output delay is more
than 1minute, it will stop output; if unit is in re-heating state, oil
pump control will always output.