HGM6510 GENSET PARALLEL UNIT
HGM6510 Genset Parallel Unit
ISSUE 2013-07-15
Version 1.7
Page 31 of 52
Parameter
Range
Default
Notes
value>Return value
27 Generator Under
Frequency (Warn)
(0.1-74.9)Hz
42.0Hz
On-load value: 45.0Hz
Setting standard:
Shutdown value<Warn
value<On-load value
28 Generator Under
Frequency (Shutdown)
(0-74.8)Hz
40.0Hz
Generator under frequency
shutdown value
29 Generator Over
Frequency (Warn)
(0.1-74.9)Hz
55.0Hz
Return value: 52.0Hz
30 Generator Over
Frequency (Shutdown)
(0.2-75)Hz
57.0Hz
Setting standard:
Shutdown value>Warn
value>Return value
31 Over Current
(50-120)%
100%
Analogue Value
32 Flywheel Teeth
(10-500)
118
Tooth number of the
engine for judging of
starter disconnect
conditions and detection of
engine speed.
33 Under Speed (Warn)
(1-5999)RPM
1350RPM
On-load value: 1380RPM
Setting standard:
Shutdown value<Warn
value<On-load value
34 Under Speed
(Shutdown)
(0-5998)RPM
1270RPM
Under speed shutdown
Value
35 Over Speed (Warn)
(1-5999)RPM
1650RPM
Return value: 1620RPM
36 Over Speed
(Shutdown)
(2-6000)RPM
1710RPM
Setting standard:
Shutdown value>Warn
value>Return value
37 Over Speed Shoot
(0-10)%
10
Analogue Value
38 Battery Under Volt
(Warn)
(0-39.9)V
8.0V
Return Value: 9.0V
39 Battery Over Volt
(Warn)
(0.1-40)V
33.0V
Return Value: 32 V
40 Charge Alternator
Failure (Warn)
(0-39)V
6.0V
Analogue Value
41 Language Select
(0-2)
0
0:Chinese; 1:English
2: Espanol
42 Password
(0-9999)
1234
Numerical Value
43 Priority
(0-19)
0
The smaller the number,
the higher the priority.
44 Module Address
(RS485)
(1-254)
1
RS485
communication
address
45 CT
(5-6000):5A
500A
Load Current: 500A
46 Rated Active Power
(0-6000)
345
Unit: kW
47 Rated Reactive
Power
(0-6000)
258
Unit: kVar