HGM6510 GENSET PARALLEL UNIT
HGM6510 Genset Parallel Unit
ISSUE 2013-07-15
Version 1.7
Page 32 of 52
Parameter
Range
Default
Notes
48 Load Ramp Rate
(0-100)%
3%
Load/unload speed %/s
49 Full Power
(0-100)%
80%
Schedule other gen-sets’
start load percentage
50 Low Power
Shutdown
(0-99)%
50%
Schedule other gen-sets’
stop load percentage
51 Positive Freq
Difference
(0-2)Hz
0.2Hz
Frequency difference
between the generator and
the bus. If it is lower than
the positive value and
higher than the negative
value, then it is considered
as synchronization.
52 Negative Freq
Difference
(0-2)Hz
0.1Hz
53 Voltage Difference
(0-30)V
3V
Voltage difference between
generator and bus.
54 Phase Angle
Difference
(0-20)°
10°
Initial phase difference
between generator and
bus.
55 Fail to Sync Delay
(5-300)s
60s
If after synchronization is
initiated, the gen-set fails to
synchronize after the delay
has expired, “Fail to Sync”
alarm will be initiated.
56 MSC Baud Rate
(0-2)
0
Baud rate of MSC
0:330K
1:250K
2:125K