HGM7100N GENSET CONTROLLER USER MANUAL 
HGM7100N Genset Controller                        2020-09-10                      Version1.2                Page 15 of 47 
6.2  SHUTDOWN ALARM 
When controller detects shutdown alarms, it immediately opens the breaker and stop the genset, at the 
same time it displays alarm type. 
Table 6 - Shutdown Alarms 
When  controller  detects  emergency  stop  signals,  it  will  send  stop 
signals. 
When controller detects the speed value is higher than the set value, 
it will send stop signals. 
When controller detects the speed value is lower than the set value, it 
will send stop signals. 
When controller detects speed value equals to 0, and action select 
“Shutdown”, it will send stop signals. 
When controller detects the frequency value is higher than the set 
value, it will send stop signals. 
When  controller detects  the  frequency value  is  lower than  the  set 
value, it will send stop signals. 
When controller detects the voltage value of genset is higher than the 
set value, it will send stop signals. 
When controller detects the voltage value of genset is lower than the 
set value, it will send stop signals. 
If genset start failure within setting of start times, controller will send 
stop signals. 
When controller detects the current value is higher than the set value 
and action select “Shutdown”, it will send stop signals. 
When maintenance time countdown equals to 0, and action select 
“Shutdown”, it will send stop signals. 
When  controller  detects  that  the  reverse  power  value  (power  is 
negative) of genset exceeds the pre-set value, and action type select 
“Shutdown”, it will send stop signals. 
When controller detects that the power value (power is positive) of 
generator-set  exceeds  the  pre-set  value,  and  action  type  select 
“Shutdown”, it will send stop signals. 
Temp. Sensor Open 
Circuit 
When controller detects sensor is open circuit, and the action select 
“shutdown”, it will send stop signals. 
When controller detects temperature of water/cylinder is higher than 
the set value, it will send stop signals. 
Oil Pressure Sensor 
Open Circuit 
When controller detects sensor is open circuit, and the action select 
“shutdown”, it will send stop signals.