HGM7100N GENSET CONTROLLER USER MANUAL 
HGM7100N Genset Controller                        2020-09-10                      Version1.2                Page 25 of 47 
Time from open mains to close generator or 
from open generator to close mains. 
Pulse  width  of  mains  closed  and  generator 
closed; 0s stands for constant output. 
Pulse  width  of  open  mains  and  open 
generator. 
It is the time to detect auxiliary contactor after 
ATS switching.   
Switch  Failure 
Warning Enabled 
Immediately  Trip 
when  Mains 
Dropout   
0: Stop Mode; 1: Manual Mode; 2: Auto Mode 
Controller address while in remote monitoring 
status. 
Communication 
Stop-bit Setting 
0: 2-bit stop bit; 1: 1-bit stop bit 
0: Simplified Chinese; 1: English; 2: Other 
This  password used  to  enter  into  advanced 
parameter setting.   
When it is 0s, LCD always light. 
Scheduled Not Run 
Setting 
SGX. For details see Table 13 
0: Warning; 1: Shutdown; 2: None 
High  Temp 
Shutdown Setting 
When  temperature  value  of  externally 
connected temperature sensor is higher than 
the  set  point,  controller  will  initiate  high 
temperature shutdown alarm (judgment only 
starts  after  safety  on  delay  expired).  Delay 
value can be set.