ATyStM - 542931D - SOCOMEC
20 EN
11.3. Network congurations
Conguration of the network is done through the ATyStM autoconguration feature. Refer to section «13.4.
Programming», page 26.
11.3.1. Three phase without neutral network
For three-phase networks without neutral (3NBL) 400Vac, a neutral must be recreated to allow the ATyS M to operate at
230Vac. To recreate the neutral, we recommend the use of quantity 2x 400VA auto-transformers connected as shown
below. The neutral position must be dened as neutral on the left or neutral on the right in advance and then wired
accordingly. The example below shows the wiring for a product congured with neutral on the left
A new product must have the neutral conguration pre-programmed as on the left or on the right at the
rst start up using a real (not a recreated) 3 phase + neutral supply.
11.3.1.1. Auto-transformer connections
Reference 1599 4121
I II
207
L32L22L12L31L21L11
L1
2 4 6 8
1
N N
3 5 7
2 4 6 8
1 3 5 7
L2 L3
208 209 210
0
230
400
-T2
400 / 230 V
400 VA
63 64 73 74
0
RM32 2P
1 A aM
RM32 2P
1 A aM
230
400
-T1
400 / 230 V
400 VA
RM1 RM2
2 A aM
2 A aM
Load
Source I Source II
ATyS t M
SI/SII availability
Inputs
Common
Inhibition
Pos. 0
order
Priority:
SI/SII
not used