8. COMMUNICATION
8.1. General information
In a standard conguration, an M-Bus connection is used to connect 250* devices to a PC or a controller over a distance of
1000 meters.
* depending on the M-BUS capacity
** depending on the number of devices and the communication speed
M-BUS
M-BUS
N 1N 1
N 2
N 1 N
n
M-Bus cabling
Cabling with repeater
≈ 1000 m or 250 devices
≈ 1000 m or 250 devices
≈ 1000 m or 250 devices
Repeater Repeater Repeater
8.2. Recommendations
Use a non-shielded JYSTY Nx2x0.8 mm twisted pair (0.5 mm²).
If the distance of 1000 m is exceeded and/or the number of devices is greater than 250, add a repeater to allow additional
devices to be connected.
If there are more than 250 units, use the secondary address only.
8.3. Communication structure
The device communicates via an M-Bus protocol which involves a dialogue in accordance with a master/slave structure. The
COUNTIS units (slaves) are compatible with the 2 primary and secondary addressing modes. You can congure the primary
and secondary addressing modes via the device's interface.
8.4. Communication tables
The communication tables and relevant notes are available on the COUNTIS E45/E46
documentation page on the website at the following address:
www.socomec.com/en/countis-e4x