15
EN
COUNTIS E45/E46 - 547983A - SOCOMEC
9.1.1. Detailed view of menu "SETUP 1"
You can change the current tariff either via the communication link or via the device's T1/2 inputs.
In the "SETUP 1" menu you can select the communication type and tariff management mode.
Press SET for 3 seconds using a screwdriver to put the device into programming mode.
The default connection is: 3.4.3 = 3 phases, 4 wires, 3 currents. Other possible connections: 3.3.3 = 3 phases, 3 wires, 3
currents or 3.3.2 = 3 phases, 3 wires, 2 currents
Press
to go to the two programming options: COM = M-Bus or DiG communication = T1/T2 inputs
L1
L2
L3
N
3 x 80A
230/400 VAC 50/60 Hz
1 2 3 4 5 6 7
NC - + - +
COM RS485
MODBUS T1/2
>
3s
x1
Connection diagram
x1
3.4.3 = 3 phases, 4 wires, 3 currents
3.3.3 = 3 phases, 3 wires, 3 currents
3.3.2 = 3 phases, 3 wires, 2 currents
x1 x1
Tariff management
selection
x1 Conrm
COM = M-Bus communication
DiG = T1/T2 inputs
>
3s
Exit menu
x1 Conrm
Y=Save setting and exit
N=Exit without saving
C=Continue without saving
9.1.2. View all of the menu "SETUP 2"
In the SETUP 2 menu, press " " for 3 seconds to put the device into programming mode.
You can go to the different screens by pressing "
":
>3s
Primary M-Bus address
Secondary M-Bus address
Communication speed
Reset partial energy to zero:
Ea+ partial (kWh) Tariff T1, T2, T3, T4
Ea+ partial (kWh)
Ea- partial (kWh) Tariff T1, T2, T3, T4
Ea- partial (kWh)
Eap partial (kVAh)
Er+ partial (kVarh)
Er- partial (kVarh)
Return to the rst menu screen, "SETUP 2"