3.3- Use of the input to control position
Example 1 : Control position (status) of a changeover switch.
Command by JBUS/MODBUS (see instruction manual: CDR27028)
Visualisation of Input 1 status (address HEX 36E )
Master request
Slave
Function
Address
Address
Number of
words
Number of
words
CRC16
High-order
Low-order
High-order
Low-order
05
03
03
6E
00
02
A416
DIRIS reply:
Slave
Function
Address
Address
Word 1
Word 2
CRC16
High-order
Low-order
05
03
02
2E
0001
0000
EE33
INPUTS
Input 1
active
OUTPUTS
5+
6-
13
14
DIRIS A40
OUT 1
4-20 mA
IN 1
Ge

Other manuals for socomec DIRIS A40

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the socomec DIRIS A40 and is the answer not in the manual?

socomec DIRIS A40 Specifications

General IconGeneral
TypeMultifunction Meter
DisplayLCD with backlight
Operating Temperature-10 to +55 °C
MountingPanel mounting
Measurement ParametersVoltage, Current, Power, Energy, Frequency
CommunicationRS485, Modbus RTU
Storage Temperature-25°C to +70°C
Protection DegreeIP20
StandardsIEC 61557-12
AccuracyClass 0.5
Dimensions96 x 96 mm

Related product manuals