MAN 06 033774 technical_guide_ DIRIS_A40_A41_C.doc40/Z41 - B 22/27
CHAPTER 5 MEMORY MODULE
5.1. Powers demands configuration (P+/P-/Q+/Q-)
Powers demand storage (load curves) is used to store and analyse consumption of electrical distribution with date
and time.
Exemple 1: Storage of active power (kWh) integrated on 10 minutes and 62 days. With
internal synchronisation (internal clock) and reading by communication.
DIRIS Configuration (see instruction manual: 876 588) :
Memorisation of positive active power (+kWh) = MEMO P+ YES (yes)
Memorisation of negative active power (+kWh) = MEMO P- NO (no)
Memorisation of positive reactive power (+kvarh) = MEMO P+ NO (no)
Memorisation of negative reactive power (-kvarh) = MEMO P- NO (no)
Synchronisation mode = MEMO TOP EXT (external)
Configuration of synchronisation top time = MEMO TIME 10’ (10 minutes)
Activation of date/time function = dAtE tIME YES (yes)
Date configuration = dAtE 31-07-06
Time configuration = tIME 15h10’35"
Reading of date and time of update of the timekeepers
Master request :
Slave
Function
Address
Address
Value
Value
CRC16
High-order
Low-order
High-order
Low-order
01
03
30
02
00
03
AB0B