EasyManuals Logo

socomec DIRIS A40 Technical Guide

socomec DIRIS A40
27 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #3 background imageLoading...
Page #3 background image
MAN 06 033774 technical_guide_ DIRIS_A40_A41_C.doc40/Z41 - B 3/27
CHAPTER 1: PULSE OUTPUTS MODULE
The DIRIS A can be equipped with 2 pulse outputs modules easily affected to active energy in kWh (EA±), reactive in kvarh (ER±)
and apparent in kVAh (ES).
The pulse outputs are configurable, with a rate of pulses of 0,1k; 1k; 10k; 100k or 1000k, and a pulse duration from 100 ms to 900
ms.
1.1 - Application:
Visualisation of positive active energy meter kWh (EA+) with PLC.
It is recommended not to exceed 1 pulse per second.
Example 1: Instantaneous power displayed by the DIRIS: 105kW
Calculation of the minimum pulse rate:
105 000 W / 3600 s = 29,17W/s
In this case a pulse weight of 100 Wh can be chosen.
DIRIS configuration (see instruction manual: 876 584 or 876 585):
Pulse output type : OUT 1 TYPE = EA+ (positive active energy)
Pulses weight = Out 1 VAL = 0,1 (0,1 kWh)
Pulses duration = Out 1 DUR = 100 (100 ms)
Example 2 : Instantaneous power displayed by the DIRIS: 1895 kW
Calculation of the minimum pulse rate:
1 895 000W / 3600s = 526.3W/s
In that example, a pulse weigh of 100Wh would be too low (that would mean 5 to 6 impulses per second) it is
necessary to program a pulse weigh of 1kWh.
DIRIS configuration (see instruction manual: 876 584 or 876 585):
Pulse output allocation : OuT 1 TYPE = EA+ (positive active energy)
Pulses weight = Out 1 VAL = 1 (1kWh)
Pulses duration = Out 1 DUR = 100 (100ms)
1
2
DIRIS A40
OUT 1
PLC

Other manuals for socomec DIRIS A40

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the socomec DIRIS A40 and is the answer not in the manual?

socomec DIRIS A40 Specifications

General IconGeneral
TypeMultifunction Meter
DisplayLCD with backlight
Operating Temperature-10 to +55 °C
MountingPanel mounting
Measurement ParametersVoltage, Current, Power, Energy, Frequency
CommunicationRS485, Modbus RTU
Storage Temperature-25°C to +70°C
Protection DegreeIP20
StandardsIEC 61557-12
AccuracyClass 0.5
Dimensions96 x 96 mm

Related product manuals