MAN 06 033774 technical_guide_ DIRIS_A40_A41_C.doc40/Z41 - B 23/27
DIRIS response:
Salve
Function
Number of
Word 1
Word 2
Word 3
CRC16
bytes
01
03
06
071F
100A
0006
11C0
07 31
10 0A
0006
July the 31th
16 h 10 minutes
00 secondes
year 2006
Reading of timekeeper for active powers P+/P- of last value
Master request :
Slave
Function
Address
Address
Value
Value
CRC16
High-order
Low-order
High-order
Low-order
01
03
30
00
00
01
8B0A
DIRIS response:
Salve
Function
Number of
Word 1
CRC16
bytes
01
03
02
004C
B9B1
Reading of last power average value on 3051 address (address 3005 + timekeeper address)
Master request :
Slave
Function
Address
Address
Value
Value
CRC16
High-order
Low-order
High-order
Low-order
01
03
30
51
00
01
DADB
Adr. 3005 + 4C = 3051
DIRIS response:
Salve
Function
Number of
Word 1
CRC16
bytes
01
03
02
16FA
3667
= 5882 in décimal without CT and VT ratio
= 5882 * (10000/5A) = 11 764 000
= 1176,4 kW on the interval 10 minutes of 4:10 pm