9.5. Emergency shutdown
NOTE!
This operations interrupts the supply to the output load from both inverters and automatic bypass.
Ups power off
Put Q3 to position 0 when it’s necessary to interrupt the power supply quickly.
Remote ups power off
It is possible to interrupt the power supply to the output load using the ADC+SL board. Refer to 'Standard features and
option' chapter.
NOTE!
To restart the UPS:
Restore the input on ADC+SL card that activate the UPO command
Make an “ALARM RESET” from MAIN MENU > CONTROLS > MAINTENANCE
Launch the START PROCEDURE from MAIN MENU > CONTROLS > UPS PROCEDURE