MODULYS XM650 - 552615A - SOCOMEC
15. TECHNICAL SPECIFICATIONS
Number of modules 2 3 4 5 6 7
Power
(N+1 redundant)
kW 100+0
(1)
100+50 150+50 200+50 250+50 300+50
kVA 100+0
(1)
100+50 150+50 200+50 250+50 300+50
Input
Input mains voltage 3ph + N 340 V to 480 V (+20/-15%) up to -40% @ 70% of nominal load
Input mains frequency Hz 40 to 70
Input power factor ≥ 0.99
(2)
Total harmonic input current
distortion (THDi)
≤ 3% (@: Pn, Resistive load, Mains THDv ≤ 1%)
Output
Output voltage
(three phase + neutral)
V 3Ph+N 380/400/415 V ±1%
(3)
Frequency Hz 50-60 Hz (selectable) ±0.01%
Total output voltage distortion
(THDv)
% ≤ 1% (Ph/Ph); ≤ 2% (Ph/N) (@: Pn, Resistive load)
Overload
(4)
10 min kW 125 187.5 250 312.5 375 437.5
1 min kW 150 225 300 375 450 525
Crest Factor ≥ 2.7
Bypass
Bypass input voltage V Nominal output voltage ±15% (±20% if GENSET is used)
Bypass input frequency Hz 50/60 +/-2% selectable (±8% if GENSET is used)
Stored energy mode of operation
Battery voltage range V From+/-180
(5)
up to+/-330
(6)
(18+18 to 24+24 VRLA battery blocks)
(7)
Environmental
Operating temperature °C 0-40 °C (+15 °C to +30 °C recommended)
Storage temperature °C –25 °C to +55 °C
Relative humidity % 95% condensation-free
Altitude (max) m 1000 (3000 with derating)
Acoustic noise (@ 70% Pn) dBA 53 50 55 56 57 58
Cooling type
Air cooling
Required cooling capacity m
3
/h 1200 1800 2400 3000 3600 4200
Dissipated power (max) W 5160 4390 6910 9430 12060 14470
Dissipated power (max) BTU/h 17610 14980 23580 32180 41160 49380
Dimensions and Weight
Dimensions (W x D x H) mm 1200 x 960 x 1990
"M5-S-650-82
(2x Bypass modules included)"
kg 572 608 644 680 716 752
"M5-S-650-88
(2x Bypass modules included)"
kg 572 608 644 680 716 752
"M5-S-650-88
(3x Bypass modules included)"
kg 596 632 668 704 740 776
UPS module kg 36
Standar
d
Safety EN/IEC 62040-1 - AS 62040-1
EMC EN/IEC 62040-2 - AS 62040-2
Pr
oduct certification IECEE CB Scheme
Performance EN/IEC 62040-3 - AS 62040-3
Product marks CE - RCM
(8)
- CMIM
(8)
- UKCA
(8)
Protective class Protective Class I
Touch current < 1 mA
Protection level IP20
(1) No redundancy
(2) Pout ≥ 50% Sn
(3) 360 V with Pout = 90% Pn
(4) Initial Condition Pout ≤ 80% Pn
(5) @ Battery Fully Discharged. Call SOCOMEC support service
(6) @ Battery Fully Charged. Call SOCOMEC support service
(7) Condition apply. For further information contact SOCOMEC
(8) Depends on the production site. Consult the data plate on the equipment.