9. OPERATING PROCEDURES
NOTE: before carrying out any operations on the unit read the 'Safety standards' chapter
carefully.
NOTE: with the stop procedure the load will be disconnected.
9.1. Switching on
Connect the mains and auxiliary mains to the UPS.
Put switch Q1 (or the external input mains switching device) into position 1.
Wait for the display to switch on.
Enter MAIN MENU > CONTROLS > UPS PROCEDURE.
Select START and press ENTER.
Carry out the operations indicated on the display.
9.2. Switching off
This operation interrupts the power supply to the load. The UPS and the battery charger will be shutdown.
Enter menu MAIN MENU > CONTROLS > UPS PROCEDURE.
Select STOP and press ENTER.
Wait approx. 2 minutes for the UPS shutdown.
NOTE: the controlled shutdown of each server connected to the LAN can be managed by
shutdown software (only with Net Vision option card).
Carry out the operations indicated on the display. This operation cannot be aborted.
9.3. Bypass operations
Switching onto maintenance bypass
This operation creates a direct connection between the UPS input and output, excluding the equipment control part. This
operation is performed in the event of:
standard maintenance.
serious failure has occurred.
WARNING! LOAD POWERED BY AUXILIARY MAINS!
Your load is exposed to mains disturbances.
Enter menu MAIN MENU > CONTROLS > UPS PROCEDURE.
Select ON MAINTENANCE BYPASS and press ENTER.
Carry out the operations indicated on the display.
NOTE!
When an external manual bypass is present:
carry out the procedure described above
put the switch to position 1