81>.S1 49.9Hz 103ms
Press “Down”
81>.S2 threshold 51.5Hz 100ms
Press “Down”
81>.S2 49.9Hz 107ms
Press “Down”
81<.S1 threshold 49.5Hz 100ms
Press “Down”
81<.S1 50.0Hz 105ms
Press “Down”
81<.S2 threshold 47.5Hz 100ms
Press “Down”
81<.S2 50.1Hz 107ms
2) Autotest STD
Select “2. Autotest STD”, then press “OK” to start Auto test STD.
The test procedure is same as Autotest Fast, but it’s much more time consuming.
3) PF Time Setting
Select “3. PF Time Setting”, then press “OK. The following will be shown on the display:
Set: *. *** s
Press “Up” or “Down” to change the 1
st
digit, press “OKto switch to next digit. After changing all digits, pressOK”.
4) QV Time Setting
Select “4. QV Time Setting”, then pressOK. The following will be shown on the display:
Set** s
Press “Up” or “Down” to change the 1
st
digit, press “OKto switch to next digit. After changing all digits, pressOK.
5) Control 81.S1
Select “5. Control 81.S1”, press “OK. Press “up” or “downto select “Enable 81.S1or “Disable 81.S1”, press “OK.