44
L20, L30
Cabinet Parallel Basic Units: Parallel cabinet number, must modify the total parallel
cabinet number after setting work mode to parallel mode. The value can only be 2,
because only two UPS systems of this model can be connected in a parallel system.
Cabinet Parallel Redundancy Units: Parallel redundancy cabinet number, can modify
the redundancy cabinet number after set work mode to parallel mode. The value canbe
0~1, default value is 0, maximum allowed value is 1, because only two UPS systems of
this model can be connected in a parallel system.
4.3.7.3.
Output setting
Output Freq: Output frequency. The value can be 50Hz or 60Hz.
Output Volt Level: Output voltage level. The value can be 220, 230 and 240.
Output Volt Adjust (%): Inverter voltage regulated. The value can be -5%~0~+5%, step
is 0.5%, default value: 0.